Profibus L2 Indoor
Applications :
-
This system cable is used to interconnect L2-BUS components.
This cable is an economical solution for the cell and field area. For the information exchange between different automation systems as well as for communication with the connected decentralized field units, serial fieldbus systems are used. The types mentioned here are suitable for indoor laying and are equipped with a special PVC jacket.
Construction :
-
Type/Area of Application Fixed Installation, Indoor Cable Construction 1x2x0.64 mm Inner Conductor Diameter Copper, bare (AWG 22/1) Conductor Insulation Foam-skin-PE Conductor Colors Red, green Stranding Element 2 conductors + 2 fillers stranded together Shielding Polyester foil, aluminum-lined Total Shielding Cu braid, tinned Outer Jacket Material PVC Outer Diameter 7.8 mm ± 0.4 mm Outer Jacket Color Grey/Violet
Electrical Data :
-
CharacteristicImpedance@3-20Hz 150 Ω ± 10 Ω Conductor Resistance 55.0 Ohm/km max. Insulation Resistance 1.00 GOhm x km min. Mutual Capacitance@1 KHz 30.0 nF/km nom. Working Voltage Max: 250 V Test Voltage 1.5 KV Attenuation 9.6 kHz < 2.5 dB/km 38.4 kHz < 4 dB/km 4 MHz < 22 dB/km 16 MHz < 42 dB/km
Technical Data :
-
Weight approximately 69.0 kg/km Min. Bending Radius (Laying) 15 x OD mm Operating Temp.Range, min. -40 °C Operating Temp.Range, max. +70 °C