Profibus SK Indoor + Outdoor
Applications :
-
The application of these Profibus SK cables are in the cell and field area, just as for conventional types. The great advantage of this new system is the quick connection of the cable to the respective plugs. This type of processing also avoids errors. The above mentioned types are suitable for indoor- or outdoor installation and are equipped with a special PVC or PE jacket.
Construction :
-
Type/Area of Application Fixed Installation, Indoor /Outdoor Cable Construction 1x2x0.64 mm Inner Conductor Diameter Copper, bare (AWG 22/1) Conductor Insulation Foam-skin-PE Conductor Colors red, green Stranding Element 2 conductors + filler Wrapping Polyester foil over stranded bundle Shielding Polyester foil, aluminum-lined Total Shielding Copper braid, tinned Outer Jacket Material PVC/PE Outer Diameter 8.0 mm ± 0.4 mm Outer Jacket Color Violet /Black
Electrical Data :
-
CharacteristicImpedance@3-20Hz 150 Ω ± 10 Ω Conductor Resistance 57.1 Ohm/km max. Insulation Resistance 1.00 GOhm x km min. Mutual Capacitance@1KHz 35.0 nF/km nom. Working Voltage 300V Test Voltage 1.5 KV Attenuation 9.6 kHz < 2.5 dB/km 38.4 kHz < 4.0 dB/km 4.0 MHz < 22.0 dB/km 16.0 MHz < 42.0 dB/km
Technical Data :
-
Weight: approximately 75.0 kg/km approximately 65.0 kg/km Min. Bending Radius (Laying) 15 x OD mm 15 x OD mm Operating Temp.Range, min. - 40 °C - 40 °C Operating Temp.Range, max. +70 °C +70 °C